AXIS#.FAULT7015.ACTION
Description
This parameter determines the action the drive should take when F7015 occurs. If it is set to 1 or 4, the velocity will still be clamped at AXIS#.VL.LIMITN.
Parameter Value | Drive Action |
---|---|
0 | Disable Amplifier |
1 | Ignore (Fault will not be reported) |
2 | Controlled Stop |
3 | Dynamic Brake |
4 | Generate Warning (See W7015) |
Versions
Action | Version | Notes |
---|---|---|
Implemented | 02-10-04-000 |
General Information
Type |
Read/Write |
Units |
N/A |
Range |
0 to 4 |
Default Value |
1 |
Data Type |
Integer |
Stored in Non-Volatile Memory |
Yes |
Variants Supported
AKD2G
Fieldbus Information
Command |
Index |
SubIndex |
Data Type |
Units |
Float Scale |
Access |
PDO Mappable |
---|---|---|---|---|---|---|---|
AXIS1.FAULT7015.ACTION |
501ch |
02h |
Unsigned8 |
- |
- |
Read/Write |
No |
AXIS2.FAULT7015.ACTION |
511ch |
02h |
Unsigned8 |
- |
- |
Read/Write |
No |
ID |
Instance |
Attribute |
Name |
Data Type |
Access |
User Mappable |
---|---|---|---|---|---|---|
7201 |
1 |
7201 (0x1c21) |
AXIS1.FAULT7015.ACTION |
Unsigned8 |
Read/Write |
Yes |
72737 |
2 |
7201 (0x1c21) |
AXIS2.FAULT7015.ACTION |
Unsigned8 |
Read/Write |
Yes |
Parameter |
PNU |
Data Type |
Access |
Units |
---|---|---|---|---|
AXIS#.FAULT7015.ACTION |
7201 |
Unsigned8 |
Read/Write |
- |