FAULT564.ACTION, FAULT565.ACTION

General Information

Type

R/W Parameter

Description

Gets/Sets the fault action for either fault 564 or 565 in the AKD-C.

Units

N/A

Range

0, 1, 4

Default Value

4

Data Type

Integer

Start Version

M_01-09-10-000

Description

These parameters set the action the AKD-C uses when the node count on string 1 (F564) or string 2 (F565) decreases. The supervision of nodes begins as soon as the nodes are powered (CPS.ACTIVE >= 3).

Value Action
0 DisableRemoval of the ENABLE signal. Disables power stage. amplifier
1 Ignore
4 Generate warning

 