General Specification

The 2-channel analog output terminal generates analog output signals in the range from 0 to 20 mA. The power is supplied to the process level with a resolution of 12 bits and is electrically isolated. Ground potential for the output channels of a Bus Terminal is common with the 24 V DC supply. The output stages are powered by the 24 V supply. This terminal combines two channels in one housing and the run LEDs give an indication of the data exchange with the Bus Coupler.

Electrical and Mechanical Specification

Electrical and Mechanical Specification
AKT-AN-220-000
Number of outputs
2
Power supply
24 V DC via the power contacts
Signal current
0…20 mA
Load
<500 Ω
Measuring error
Conversion time
~ 1.5 ms
Resolution
12 bits
Electrical isolation
500 Vrms (Standard Bus/signal voltage)
Current consump. from Standard Bus
typ. 60 mA
Bit width in the process image
output: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration
no address or configuration settings
Weight
80 g
Operating/storage temperature
0 C ... +55 °C /-25 °C... +85 °C
Relative humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27/ 29
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class / installation pos.
IP 20 / variable