General Specification
The 2-channel output terminal has two relays each of which has a single contact. The relay contact is connected to the power contacts, which are suitable for use at up to 230 V AC, and can be generally used for switching devices requiring mains power. The Bus Terminal indicates its signal state by means of a light emitting diode. The Bus Terminals have potential-free contacts. The power contacts are not looped through.
Electrical and Mechanical Specification
Electrical and Mechanical Specification | AKT-DT-2RT-000 |
---|---|
Number of outputs
|
2 x make contacts
|
Rated load voltage
|
230 V AC/30 V DC
|
Ohmic switching current
|
5 A AC/DC
|
Inductive switching current
|
2 A AC/DC
|
Minimum permitted load
|
10 mA at 5 V DC
|
Lamp test, electronic ballast
|
4 x 58 W
|
Electrical isolation
|
500 Vrmsrms stands for root mean square (also known as the quadratic mean) (Standard Bus / field potential)
|
Current consump. from Standard Bus
|
85 mA
|
Bit width in the process image
|
2 outputs
|
Operating cycles mech. (min.)
|
2 x 107
|
Operating cycles electr. (min.)
|
1 x 105 (5 A/30 V DC)
|
Configuration
|
no address or configuration settings
|
Weight approx.
|
80 g
|
Operating/storage temperature
|
0 C ... +55 °C /-25 °C... +85 °C
|
Relative humidity
|
95 %, no condensation
|
Vibration/shock resistance
|
conforms to EN 60068-2-6 / EN 60068-2-27/ 29
|
EMC immunity/emission
|
conforms to EN 61000-6-2 / EN 61000-6-4
|
Protect. class/installation pos.
|
IP 20 / variable
|
Pluggable
|
For all Bus Terminals
|