General Specification

The 2-channel output terminal has two relays each of which has a single contact. The relay contact is connected to the power contacts, which are suitable for use at up to 230 V AC, and can be generally used for switching devices requiring mains power. The Bus Terminal indicates its signal state by means of a light emitting diode. The Bus Terminals have potential-free contacts. The power contacts are not looped through.

Electrical and Mechanical Specification

Electrical and Mechanical Specification AKT-DT-2RT-000
Number of outputs
2 x make contacts
Rated load voltage
230 V AC/30 V DC
Ohmic switching current
5 A AC/DC
Inductive switching current
2 A AC/DC
Minimum permitted load
10 mA at 5 V DC
Lamp test, electronic ballast
4 x 58 W
Electrical isolation
Current consump. from Standard Bus
85 mA
Bit width in the process image
2 outputs
Operating cycles mech. (min.)
2 x 107
Operating cycles electr. (min.)
1 x 105 (5 A/30 V DC)
Configuration
no address or configuration settings
Weight approx.
80 g
Operating/storage temperature
0 C ... +55 °C /-25 °C... +85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27/ 29
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class/installation pos.
IP 20 / variable
Pluggable
For all Bus Terminals