General Specification

The power feed terminals make it possible to set up various potential groups with the standard voltages of 24 V DC. The power feed terminals are available with or without fine-wire fuse. In order to monitor the supply voltage, the terminals with diagnostics report the status of the power feed terminal to the Bus Coupler through two input bits. It is thus possible for the controller to check the distributed peripheral voltage over the fieldbus.

Electrical and Mechanical Specification

Electrical and Mechanical Specification AKT-PS-024-000 AKT-PSF-024-000
Nominal voltage
24 V DC
24 V DC
Integrated fine-wire fuse
-
...6.3A
Diagnostics
-
yes
Power LED
green
green
Defect LED
-
red
Reported to Standard Bus
-
yes
PE contact
yes
yes
Shielding connection
-
-
Renewed infeed
yes
yes
Connection facility to additional power contact
1
1
Standard Bus loped through
yes
yes
Logical width in process image
0
2
Connection to top-hat rail
-
-
Electrical isolation
yes
yes
Housing width in mm
12
12
Side by side mount. on Bus Terminals with pow. contact
yes
yes
Side by side mount. on Bus Terminals without pow. contact
yes
yes