IL.MI2T

Description

This parameter returns the motor I2t load in percent. The supplied current will be limited by ILClosed"Instruction list" This is a low-level language and resembles assembly.MIFOLD to MOTOR.ICONT case that the load reaches a value of 100%. The current limit IL.MIFOLD will be restored to MOTOR.IPEAK in case that the load falls under 95%.

General Information

Type

R/O parameter

Units

%

Range

0 to 100%

Default Value

N/A

Data Type

Float

See Also

IL.MIMODE, IL.MI2TWTHRESH

Start Version

M_01-04-01-000

FieldbusClosedA Fieldbus is an industrial network system for real-time distributed control (e.g. CAN or Profibus). It is a way of connecting instruments in a plant design Index/Subindex Object Start Version

EtherCATClosedEtherCAT is an open, high-performance Ethernet-based fieldbus system. The development goal of EtherCAT was to apply Ethernet to automation applications which require short data update times (also called cycle times) with low communication jitter (for synchronization purposes) and low hardware costs COE and CANopen

3427h/3