AKT2G-DN-008-000

8-channel Digital Input Terminal 24 V DC, filter 3.0 ms, 1-wire system

The DN-008 digital input terminal acquires binary control signals from the process level and transmit them, in an electrically isolated form, to the higher-level automation device. The digital input terminals of the DN-008 feature an input filter (3 ms) and indicate their signal state through an LED for each channel.

LEDs

LED Color Meaning

INPUT 1- 8

green

off

Signal voltage "0" (-3 V ... 5 V)

on

Signal voltage "1" (11 V ... 30 V)

Connection

Terminal Point Description
Name No.

Input 1

1

Input 1

Input 3

2

Input 3

Input 5

3

Input 5

Input 7

4

Input 7

Input 2

5

Input 2

Input 4

6

Input 4

Input 6

7

Input 6

Input 8

8

Input 8

Technical Data

Technical Data

AKT2G-DN-008-000

Number of inputs 8
Number of simultaneously controllable in- puts, depending on the ambient temperature 8 (-25°C ... +55°C) 4 (> +55°C ) (aligned in horizontal installation position)
Nominal voltage of the inputs 24 VDC (-15% / +20%)
Signal voltage "0" -3 V ... 5 V (EN 61131-2, type 1/3)
Signal voltage "1" 11 V ... 30 V (EN 61131-2, type 1/3)
Input filter 3 ms
Input current typically 3 mA (EN 61131-2, type 1/3)
Current consumption power contacts typ. 2 mA + load
Current consumption via E-bus typ. 90 mA
Electrical isolation 500 V (E-bus/field voltage)
Bit width in the process image 8 input bits
Configuration no address setting, configuration via TwinCAT System Manager
Weight approx. 55 g
Permissible ambient temperature range during operation -25°C ... +60°C (extended temperature range, aligned in horizontal installation position) -25°C ... +45°C (all other installation positions)
Permissible ambient temperature range during storage -40°C ... +85°C
Permissible relative humidity 95%, no condensation
Dimensions (W x H x D) approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance according to EN 60068-2-6/EN 60068-2-27, see also Installation instructions for terminals with increased mechanical load capacity
EMC resistance burst/ESD conforms to EN 61000-6-2 / EN 61000-6-4
Protection class IP20
Installation position see note Constraints regarding installation position and operating temperature range
Approval CE, cULus, ATEX, IECEx

Related Topics: Map Input and Output to Variables