AKT-AT-220-000

General Specification

2-channel analog output terminals 4...20 mA.

The 2-channel analog output terminal generates analog output signals in the range from 0 to 20 mA.

  • The power is supplied to the process level with a resolution of 12-bits and is electrically isolated.
  • Ground potential for the output channels of a Bus Terminal is common with the 24 V DC supply.
  • The output stages are powered by the 24 V supply.
  • This terminal combines two channels in one housing.
  • The run LEDs give an indication of the data exchange with the Bus Coupler.

Electrical and Mechanical Specification

Electrical and Mechanical Specification

Description

Bit width in the process image

Output: 2 x 16 bit data (2 x 8 bit control/status optional)

Configuration

No address or configuration settings

Conversion time

~ 1.5 ms

Current consumption from Standard Bus

Typ. 60 mA

Electrical isolation

500 Vrms (Standard Bus/signal voltage)

EMC immunity / emission

Conforms to EN 61000-6-2 / EN 61000-6-4

Load

<500 Ω

Measuring error

Number of outputs

2

Operating / storage temperature

0 C ... +55 °C /-25 °C... +85 °C

Power supply

24 V DC via the power contacts

Protect. class / installation pos.

IP 20 / variable

Relative humidity

95 %, no condensation

Resolution

12 bits

Signal current

0…20 mA

Vibration / shock resistance

Conforms to EN 60068-2-6 / EN 60068-2-27/ 29

Weight

80 g