AKT-AT-410-000 / AKT-AT-810-000

General Specification

4/8-channel analog output terminals 0...10VDC.

Electrical and Mechanical Specification


Electrical and Mechanical Specification

AKT-AT-410-000

AKT-AT-810-000

Bit width in the process image

Output: 4 x 16 bit data (4 x 8 bit control / status optional)

Output: 8 x 16 bit data (8 x 8 bit control / status optional)

Configuration

No address or configuration setting

 

Conversion time

~ 4 ms

~ 8 ms

Current consumption from Standard Bus

20 mA

 

Electrical isolation

500 Vrms (Standard Bus/signal voltage)

 

EMC immunity/emission

Conforms to EN 61000-6-2 / EN 61000-6-4

 

Load

>5 Ω (short-circuit-proof)

 

Measuring error

< ±0.1 % (relative to full scale value)

< ±0.2 % (relative to full scale value)

Number of outputs

4

8

Operating / storage temperature

0 C ... +55 °C /-25 °C... +85 °C

 

Pluggable wiring

for all Bus Terminals

 

Protect. class / installation pos.

IP 20 / variable

 

Relative humidity

95 %, no condensation

 

Resolution

12 bits

 

Signal voltage

0…10 V

 

Vibration / shock resistance

Conforms to EN 60068-2-6 / EN 60068-2-27/ 29

 

Weight

75 g