General Specification

2-channel relay output terminals 230VAC, 2A

  • The 2-channel output terminal has two relays each of which has a single contact.
  • The relay contact is connected to the power contacts, which are suitable for use at up to 230 V AC, and can be generally used for switching devices requiring mains power.
  • The Bus Terminal indicates its signal state by means of a light emitting diode.
  • The Bus Terminals have potential-free contacts.
  • The power contacts are not looped through.

Electrical and Mechanical Specification

Electrical and Mechanical Specification

AKT-DT-2RT-000

Bit width in the process image

2 outputs

Configuration

no address or configuration settings

Current consumption from Standard Bus

85 mA

Electrical isolation

500 VrmsClosed rms stands for root mean square (also known as the quadratic mean) (Standard Bus / field potential)

EMC immunity / emission

Conforms to EN 61000-6-2 / EN 61000-6-4

Inductive switching current

2 A AC/DC

Lamp test, electronic ballast

4 x 58 W

Minimum permitted load

10 mA at 5 V DC

Number of outputs

2 x make contacts

Ohmic switching current

5 A AC/DC

Operating cycles electr. (min.)

1 x 105 (5 A/30 V DC)

Operating cycles mech. (min.)

2 x 107

Operating / storage temperature

0 C ... +55 °C /-25 °C... +85 °C

Pluggable

For all Bus Terminals

Protect. class / installation pos.

IP 20 / variable

Rated load voltage

230 V AC/30 V DC

Relative humidity

95 %, no condensation

Vibration / shock resistance

Conforms to EN 60068-2-6 / EN 60068-2-27/ 29

Weight approx.

80 g