AKT-DT-2RT-000
General Specification
2-channel relay output terminals 230VAC, 2A
- The 2-channel output terminal has two relays each of which has a single contact.
- The relay contact is connected to the power contacts, which are suitable for use at up to 230 V AC, and can be generally used for switching devices requiring mains power.
- The Bus Terminal indicates its signal state by means of a light emitting diode.
- The Bus Terminals have potential-free contacts.
- The power contacts are not looped through.
Electrical and Mechanical Specification
|
Electrical and Mechanical Specification |
AKT-DT-2RT-000 |
|---|---|
|
Bit width in the process image |
2 outputs |
|
Configuration |
no address or configuration settings |
|
Current consumption from Standard Bus |
85 mA |
|
Electrical isolation |
500 Vrms |
|
EMC immunity / emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
|
Inductive switching current |
2 A AC/DC |
|
Lamp test, electronic ballast |
4 x 58 W |
|
Minimum permitted load |
10 mA at 5 V DC |
|
Number of outputs |
2 x make contacts |
|
Ohmic switching current |
5 A AC/DC |
|
Operating cycles electr. (min.) |
1 x 105 (5 A/30 V DC) |
|
Operating cycles mech. (min.) |
2 x 107 |
|
Operating / storage temperature |
0 C ... +55 °C /-25 °C... +85 °C |
|
Pluggable |
For all Bus Terminals |
|
Protect. class / installation pos. |
IP 20 / variable |
|
Rated load voltage |
230 V AC/30 V DC |
|
Relative humidity |
95 %, no condensation |
|
Vibration / shock resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27/ 29 |
|
Weight approx. |
80 g |