AKT2G-DT-008-000

8-channel Digital Output Terminal 24 V DC, 0.5 A, 1-wire system

The AKT2G-DT-008 digital output terminal relays binary control signals of the automation device in an electrically isolated manner to the actuatorsClosed A mechanical device for moving or controlling a mechanism or system. An actuator typically is a mechanical device which transforms an input signal (usually an electrical signal) into motion of the process level. They are protected against reverse polarity at the power contacts. The digital output terminals of the device indicate their signal state through an LED for each channel.

Related Topics: Map Input and Output to Variables

AKT2G-DT-008 LEDs and Connection

LEDs

LED

Color

Meaning

OUTPUT 1- 8

green

off

No output signal

on

24 VDC output signal at the respective output

Connection

Terminal point Description
Name No.

Output 1

1

Output 1

Output 3

2

Output 3

Output 5

3

Output 5

Output 7

4

Output 7

Output 2

5

Output 2

Output 4

6

Output 4

Output 6

7

Output 6

Output 8

8

Output 8

Technical Data

Technical Data

AKT2G-DT-008-000

Number of outputs

8

Non-reactive outputs

yes (see Interference-Free EtherCAT Terminals)

Load type

ohmic, inductive, lamp load

Nominal output voltage

24 VDC (-15% / +20%)

Switching times

TON: 60 µs typ.; TOFF: 300 µs typ.

Output current per channel

maximum 0.5 A (short-circuit proof)

Switch-off energy (inductive)

max. 150 mJ/channel

Current consumption from load voltage (power contacts)

typ. 15 mA

Supply voltage for electronic

via the E-Bus

Current consumption via E-bus

typ. 110 mA

Electrical isolation

500 V (E-bus/field voltage)

Bit width in the process image

8 output bits

Configuration

no address setting, configuration via KAS IDEClosed "Integrated development environment" An integrated development environment is a type of computer software that assists computer programmers in developing software. IDEs normally consist of a source code editor, a compiler and/or interpreter, build-automation tools, and a debugger

Weight

approx. 55 g

Permissible ambient temperature range during operation

Aligned in horizontal installation position:

-25°C ... +60°C (extended temperature range)

All other installation positions: -25°C ... +45°C

Permissible ambient temperature range during storage

-40°C ... +85°C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

according to EN 60068-2-6/EN 60068-2-27,

see also Installation instructions for terminals with increased mechanical load capacity

EMC resistance burst/ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

see note Constraints regarding installation position and operating temperature range

Approval

CE, cULus, ATEX