AKT-AT-220-000
General Specifications
2-channel analog output terminals 4 to 20mA.
The 2-channel analog output terminal generates analog output signals in the range from 0 to 20mA.
- The power or voltage is supplied to the process level with a resolution of 12-bits and is electrically isolated.
- Ground potential for the output channels of a Bus Terminal is common with the 24VDC supply.
- Output stages are powered by the 24VDC supply.
- This terminal combines two channels in one housing.
- Run LEDs indicate the data exchange with the Bus Coupler.
Electrical and Mechanical Specification
Electrical and Mechanical Specification |
Description |
---|---|
Bit Width in the Process Image |
|
Configuration |
No address or configuration settings. |
Conversion Time |
~1.5ms |
Current Consumption from Standard Bus |
Typ. 60mA |
Electrical Isolation |
500Vrms (Standard Bus / Signal Voltage). |
EMC Immunity / Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4. |
Load |
<500Ω |
Measuring Error |
|
Number of Outputs |
2 |
Operating / Storage Temperature |
|
Power Supply |
24VDC using the power contacts. |
Protect Class / Installation pos. |
IP 20 / variable. |
Relative Humidity |
95%, no condensation. |
Resolution |
12-bits |
Signal Current |
0 to 20mA |
Vibration / Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27/ 29. |
Weight |
80 g |