AKT-DT-2RT-000
General Specifications
2-channel relay output terminals 230VAC, 2A.
- 2-channel output terminal has two relays, each with a single contact.
- The relay contact is connected to the power contacts.
- These contacts are suitable for use at up to 230VAC and can be used for switching devices requiring mains power.
- The Bus Terminal indicates its signal state by means of a light emitting diode.
- The Bus Terminals have potential-free contacts.
- The power contacts are not looped through.
Electrical and Mechanical Specification
Electrical and Mechanical Specification |
AKT-DT-2RT-000 |
---|---|
Bit Width in the Process Image |
2 outputs |
Configuration |
No address or configuration settings. |
Current Consumption from Standard Bus |
85mA |
Electrical Isolation |
500Vrms (Standard Bus / Field Potential) |
EMC Immunity / Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4. |
Inductive Switching Current |
2A AC/DC |
Lamp Test, Electronic Ballast |
4 x 58W |
Minimum Permitted Load |
10mA at 5VDC |
Number of Outputs |
2 x make contacts |
Ohmic Switching Current |
5A AC/DC |
Operating Cycles Electrical (min.) |
1 x 105 (5A/30VDC) |
Operating Cycles Mechanical (min.) |
2 x 107 |
Operating / Storage Temperature |
|
Pluggable Wiring |
For all Bus Terminals. |
Protect Class / Installation pos. |
IP 20 / variable. |
Rated Load Voltage |
|
Relative Humidity |
95%, no condensation. |
Vibration / Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27/ 29. |
Weight approx. |
80g |