AKT2G-AN-240 CoE Object Description
Jump to a section on this page:
-
-
Relevant Objects
The object description refers to the analog input terminals for Pt100 (RTD) in 1 to 8 channel versions. Observe the indices with regard to the objects relevant for the respective terminal (channel dependent).
Introduction
The CoE overview contains objects for different intended applications:
- Objects required for parameterization and profile-specific objects required during commissioning
- Objects for indicating internal settings (may be fixed)
The following section first describes the objects required for normal operation, followed by a complete overview of missing objects.
Objects for Commissioning
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
---|---|---|---|---|---|
1011:0 |
Restore default parameters |
Restore default parameters |
UINT8 |
RO |
0x01 (1dec) |
1011:01 |
SubIndex 001 |
If this object is set to "0x64616F6C" in the set value dialog, all backup objects are reset to their delivery state. |
UINT32 |
RW |
0x00000000 (0dec) |
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
---|---|---|---|---|---|
80n0:0 |
RTD Settings |
Maximum subindex |
UINT8 |
RO |
0x1B (27dec) |
80n0:01 |
Enable user scale |
User scale is active. |
BOOLEAN |
RW |
0x00 (0dec) |
Presentation |
0: Signed presentation 1: Absolute value with MSB as sign Signed amount representation 2: High resolution (1/100 C°) [default for |
BIT3 |
RW |
0x00 (0dec) |
|
80n0:05 |
Siemens bits |
The S5 bits are superimposed on the three low-order bits (value60n0:11) Bit 0 = 1 (“overrange” or “underrange”) Bit 1 (not used) Bit 2 (not used) |
BOOLEAN |
RW |
0x00 (0dec) |
80n0:06* |
Enable filter |
Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary |
BOOLEAN |
RW |
0x00 (0dec) |
80n0:07* |
Enable limit 1 |
The status bits are set in relation to Limit 1 |
BOOLEAN |
RW |
0x00 (0dec) |
80n0:08* |
Enable limit 2 |
The status bits are set in relation to Limit 2 |
BOOLEAN |
RW |
0x00 (0dec) |
8010:09* |
Enable automatic calibration |
A calibration is cyclically started. (optional) |
BOOLEAN |
RW |
0x00 (0dec) |
80n0:0A |
Enable user calibration |
Enabling of the user calibration |
BOOLEAN |
RW |
0x00 (0dec) |
80n0:0B |
Enable vendor calibration |
Enabling of the vendor calibration |
BOOLEAN |
RW |
0x01 (1dec) |
80n0:11 |
User scale offset |
User scaling offset |
INT16 |
RW |
0x0000 (0dec) |
80n0:12 |
User scale gain |
This is the user scaling gain. The gain is represented in fixed-point format, with the factor 2-16. The value 1 corresponds to 65535 (0x00010000). |
INT32 |
RW |
0x00010000 (65536dec) |
80n0:13* |
Limit 1 |
First limit value for setting the status bits (resolution 0.1 °C) |
INT16 |
RW |
0x0000 (0dec) |
80n0:14* |
Limit 2 |
Second limit value for setting the status bits (resolution 0.1 °C) |
INT16 |
RW |
0x0000 (0dec) |
80n0:15 |
Filter settings |
This object determines the digital filter settings, if it is active via Enable filter (index 0x80n0:06). The possible settings are sequentially numbered.
|
UINT16 | RW | 0x0000 (0dec) |
80n0:17 |
User calibration offset |
User offset calibration |
INT16 |
RW |
0x0000 (0dec) |
80n0:18 |
User calibration gain |
User gain compensation |
UINT16 |
RW |
0xFFFF (65535dec) |
80n0:19 | RTD element |
RTD Element
|
UINT16 | RW | 0x0000 (0dec) |
80n0:1A | Connection technology |
Connection technology
|
UINT16 | RW | 0x0000 (0dec) |
80n0:1B | Wire calibration 1/32 Ohm | Calibration of the supply lines | INT16 | RW | 0x0000 (0dec) |
-
-
The filter properties are set only via index 0x8000:15
The filter frequencies are set for all channels of the AN-240 terminals centrally via index 0x8000:15 (channel 1).
The corresponding indices 8010:15 of the AN-240 have no parameterization function!
Profile-specific objects (0x6000-0xFFFF)
The profile-specific objects have the same meaning for all EtherCAT slaves that support the profile 5001.
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
---|---|---|---|---|---|
60n0:0 |
RTD Inputs |
Maximum subindex |
UINT8 |
RO |
0x11 (17dec) |
60n0:01 |
Underrange |
The measuring range is undershot. |
BOOLEAN |
RO |
0x00 (0dec) |
60n0:02 |
Overrange |
The measuring range is overshot. (“open circuit” detection if “error” [index 0x60n0:07]) is set |
BOOLEAN |
RO |
0x00 (0dec) |
60n0:03* |
Limit 1 |
Limit value monitoring
|
BIT2 |
RO |
0x00 (0dec) |
60n0:05* |
Limit 2 |
Limit value monitoring
|
BIT2 |
RO |
0x00 (0dec) |
60n0:07 |
Error |
The error bit is set if the data is invalid. |
BOOLEAN |
RO |
0x00 (0dec) |
60n0:0F |
TxPDO State |
Validity of the data of the associated TxPDO (0 = valid, 1 = invalid). |
BOOLEAN |
RO |
0x00 (0dec) |
60n0:10 |
TxPDO Toggle |
The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated. |
BOOLEAN |
RO |
0x00 (0dec) |
Value |
The analog input data |
INT16 |
RO |
0x00 (0dec) |