AKT2G-PSF-024-000

Power Supply Terminal with fuse, 24 V DC

The AKT2G-PSF-024 feed terminal can be positioned at any location between the input and output terminals for establishing a further potential group or for supplying the terminals following on the right in applications with high current load. The E-Bus is looped through.

See Also:

Connections

Terminal Point Description
Indication Number
+24 V 1 Supply input + 24 V (connected internally with terminal 4 and positive power contact)
0 V 2 0 V for supply input (connected internally with terminal 5 and negative power contact)
PE 3 PE (connected internally with terminal 6 and PE power contact)
+24 V 4 Supply input + 24 V (connected internally with terminal 1 and positive power contact)
0 V 5 0 V for supply input (connected internally with terminal 2 and negative power contact)
PE 6 PE (connected internally with terminal 3 and PE power contact)

LEDs

LED Color Meaning
Power LED green off No input voltage at supply input
on 24 VDC at supply input
Error LED red off Fuse OK
on Fuse error

Technical Data

Technical Data

AKT2G-PSF-024-000

Nominal voltage 24 VDC
Power contact current load max. 10 A
Electrical isolation 500 V (E-bus/field potential)
Integrated fine-wire fuse yes; 6.3 A
Current consumption from E-Bus -
Bit width in the process image -
Configuration no address or configuration settings
Power LED yes
Diagnosis (fuse) yes, Error LED
Electrical connection to mounting rail no
PE contact yes
Renewed infeed yes
Connection facility to additional power contact 1
Side by side mounting on Bus Terminals with power contact yes
Side by side mounting on Bus Terminals without power contact yes
Weight approx. 55 g
Permissible ambient temperature range (during operation) 0°C ... +55°C
Permissible ambient temperature range (during storage) -25°C ... +85°C
Permissible relative humidity 95%, no condensation
Dimensions (W x H x D) approx. 15mm x 100mm x 70mm (width aligned: 12mm)
Mounting on 35mm mounting rail conforms to EN 60715
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC resistance burst/ESD conforms to EN 61000-6-2/EN 61000-6-4
Protection class IP 20
Installation position variable, see Positioning of Passive Terminals
Approval CE, ATEX, cULus

  • Hazard to individuals and devices!

    When designing a Bus Terminal block with different potentials on the power contacts (e.g., 230 V AC and 24 V DC), please note that it is mandatory to use potential separation terminals!
    Bring the bus system into a safe, powered down state before starting installation, disassembly, or wiring of the Bus Terminals!