AKT2G-PSF-024-000
Power Supply Terminal with fuse, 24 V DC
The AKT2G-PSF-024 feed terminal can be positioned at any location between the input and output terminals for establishing a further potential group or for supplying the terminals following on the right in applications with high current load. The E-Bus is looped through.
See Also:
Connections
Terminal Point | Description | |
---|---|---|
Indication | Number | |
+24 V | 1 | Supply input + 24 V (connected internally with terminal 4 and positive power contact) |
0 V | 2 | 0 V for supply input (connected internally with terminal 5 and negative power contact) |
PE | 3 | PE (connected internally with terminal 6 and PE power contact) |
+24 V | 4 | Supply input + 24 V (connected internally with terminal 1 and positive power contact) |
0 V | 5 | 0 V for supply input (connected internally with terminal 2 and negative power contact) |
PE | 6 | PE (connected internally with terminal 3 and PE power contact) |
LEDs
LED | Color | Meaning | |
---|---|---|---|
Power LED | green | off | No input voltage at supply input |
on | 24 VDC at supply input | ||
Error LED | red | off | Fuse OK |
on | Fuse error |
Technical Data
Technical Data |
AKT2G-PSF-024-000 |
---|---|
Nominal voltage | 24 VDC |
Power contact current load | max. 10 A |
Electrical isolation | 500 V (E-bus/field potential) |
Integrated fine-wire fuse | yes; 6.3 A |
Current consumption from E-Bus | - |
Bit width in the process image | - |
Configuration | no address or configuration settings |
Power LED | yes |
Diagnosis (fuse) | yes, Error LED |
Electrical connection to mounting rail | no |
PE contact | yes |
Renewed infeed | yes |
Connection facility to additional power contact | 1 |
Side by side mounting on Bus Terminals with power contact | yes |
Side by side mounting on Bus Terminals without power contact | yes |
Weight | approx. 55 g |
Permissible ambient temperature range (during operation) | 0°C ... +55°C |
Permissible ambient temperature range (during storage) | -25°C ... +85°C |
Permissible relative humidity | 95%, no condensation |
Dimensions (W x H x D) | approx. 15mm x 100mm x 70mm (width aligned: 12mm) |
Mounting | on 35mm mounting rail conforms to EN 60715 |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC resistance burst/ESD | conforms to EN 61000-6-2/EN 61000-6-4 |
Protection class | IP 20 |
Installation position | variable, see Positioning of Passive Terminals |
Approval | CE, ATEX, cULus |
-
-
Hazard to individuals and devices!
When designing a Bus Terminal block with different potentials on the power contacts (e.g., 230 V AC and 24 V DC), please note that it is mandatory to use potential separation terminals!
Bring the bus system into a safe, powered down state before starting installation, disassembly, or wiring of the Bus Terminals!