Description

This parameter allows the user to see the actual level of the output signal, when the IO is set to output mode. Parameter value is 0 if signal is low and 1 if signal is high. DIOx.INV can affect the signals driven onto the X9 connector.

This parameter can be read at any time. The value is only guaranteed to correspond to the output on the X9 connector when DRV.EMUEMODE is set to 10 and the DIOX.DIR is 0.

General Information

Type

NV parameter

Units

N/A

Range

0 to 1

Default Value

0

Data Type

U8

Start Version

M_01-05-00-000

Variants Supported

Variant Supported
AKD Base Yes
AKD with Position Indexer Yes
AKD EtherCAT Yes
AKD CANopen Yes
AKD BASIC Yes
AKD SynqNet Yes*
AKD EtherNet/IP Yes
AKD PROFINET Yes
AKD Sercos® III Yes
AKD-N No
AKD-C No

*In SynqNet, a parameter may be available in the firmware but have no effect on the system. See SynqNet Supported Parameters.

Fieldbus Information

If your drive type is listed as supported but no index, address, or instance number is listed, then this parameter is accessible through WorkBench, but not over your fieldbus type. For information on SynqNet parameters see SynqNet Supported Parameters.

PROFINET and Sercos® III
Parameter Fieldbus Address Attributes Signed?
DOUT9.STATE

PROFINET

2782 Byte No
Sercos® III 2 Octets
DOUT10.STATE

PROFINET

2728 Byte
Sercos® III 2 Octets
DOUT11.STATE

PROFINET

2730 Byte
Sercos® III 2 Octets
EtherNet/IP
Parameter Instance Data Size Data Type
DOUT9.STATE 783 1 Byte Integer
DOUT10.STATE 729
DOUT11.STATE 731
Modbus
Parameter Register Address Is 64 bit? Attributes Signed? Object Start Version
DOUT9.STATE 1564 No 8 bit No M_01-06-03-000
DOUT10.STATE 1456
DOUT11.STATE 1460